Short-Circuit Test System for Transformers
The HVEX Short-Circuit Test System verifies the ability of distribution transformers — dry-type or oil-immersed, up to 2500 kVA and 36 kV — to withstand the mechanical and thermal stresses of an external short circuit, per IEC 60076-5, ABNT NBR 5356-5 and ANSI C57.12.90. The system combines an energy-storage power supply, an intermediate transformer, remote control and waveform acquisition. The supply stores energy from the grid and releases it at the moment of the test, so a 380 V input of up to 500 A is enough, with no dedicated substation. The HV terminals of the transformer under test are connected to the intermediate transformer output and the LV terminals are short-circuited — or the reverse. The operator runs each application remotely, and the acquisition records the HV-side voltage and the HV and LV currents. Each laboratory is sized for the power and voltage of the transformers, the required current and duration, the applicable standards, the available supply and the facility layout.