HVEX

Command Palette

Search for a command to run...

HVEX | a8dfe8c8-5730-49a0-a9cd-bd532370857e-laboratorio-ensayo-pararrayos-01.png

TEST LABS

Routine Testing Laboratory for Metal Oxide Distribution Surge Arresters up to 36.2 kV

The laboratory is an end-to-end quality control solution for manufacturers of surge arresters, replacing time-consuming manual testing with a single, automated, and safe test cell. Manufactured by HVEX—recognized as the only domestic manufacturer of medium- and high-voltage laboratory equipment—the system eliminates production line bottlenecks by integrating electrical, electronic, control, and automation components into a single system. Its key advantages include competitive pricing, technical expertise, and the ability to customize the system to meet specific customer needs, in addition to a manufacturer’s warranty and dedicated technical support. Power-frequency reference-voltage testing (50 or 60 Hz) uses a frequency inverter. Partial-discharge testing uses a voltage regulator. The power supply is available at 50 or 60 Hz, according to the requested configuration. Approximate installation area: 6.5 m².

Technical Information

01 Requirement
Approximately 6.5 m² of floor space, with clearance compatible with the approximately 2.2 m equipment height (plus the 0.37 m signal tower).
02 Requirement
220 V power supply at 50 or 60 Hz, according to the requested configuration. Frequency inverter for power-frequency reference-voltage testing; voltage regulator for partial-discharge testing. Supply conditions and filters are defined according to the test circuit provided.
03 Requirement
Proper grounding system: Terminals H0 and Y1 (measurement) must remain permanently grounded and monitored by precision current transformers—disconnecting the ground or a current transformer failure will result in equipment damage.
04 Requirement
Safety zone maintaining a minimum distance of 2.5 meters from any live high-voltage equipment.
05 Requirement
A computer connected to the laboratory network to run the APLICADA software and monitor the tests.

About the Laboratory

The laboratory is a compact, enclosed structure, assembled from aluminum profiles with blue HVEX panels and transparent enclosures, measuring 2.2 m in height (plus 0.37 m for the signal column), 3.31 m in length, and 1.96 m in width. Internally, it is organized into sequential stations connected by a conveyor belt: entry station, test station, laser marking station, and exit stations (pass and fail). The test specimen enters via the conveyor belt, passes under the high-voltage connector for testing, proceeds to the laser marking station, and, finally, is directed to the “pass” bin or ejected to the “fail” bin—all automatically.

HVEX | 62b0a8cd-49ec-470b-8994-662251c06ae9-laboratorio-ensayo-pararrayos-vista-general.png
HVEX | 92b2e0a9-94a4-440e-8b47-dd85c657ff8f-laboratorio-ensayo-pararrayos-beneficios.png

Benefits and Usability

  • HVEX | Automatic Validation
    Automatic Validation

    The main benefit is to automatically verify the insulation capacity of the surge arresters, ensuring the safety and quality of the final product and preventing production bottlenecks. Approval/rejection is automatic, with physical separation of products and a real-time counter for approved and rejected quantities. In terms of usability, operation is simplified by a control panel with just a few buttons (on/off, start/stop conveyor, safety reset, and emergency stop) and LED indicators. All test data is saved and can be exported as a report using the APLICADA software, and a graduated column with a ruler allows for quick adjustment of the laser engraver’s height to accommodate different test specimen models (between 125 mm and 310 mm in height).