MEASUREMENT AND MONITORING
Low-Power Current Transformer (LPCT) — Electronic Current Sensor for MV Switchgear
The HVEX low-power current transformer (LPCT) measures primary current on medium-voltage networks up to 36 kV and delivers a low-power signal (333 mV) to protection relays, recloser controls and power meters. With no saturable iron core, it stays linear from load current up to fault currents of 25 kA, free from the saturation, resonance and remanence issues of inductive CTs. Compact and lightweight, it is designed for MV switchgear and panels, compact substations, reclosers and feeder protection schemes. For conventional relays, versions with 1 A or 5 A output are available through an optional amplifier. Reference standards: IEC 61869-10 (low-power passive current transformers), IEC 60529 (degree of protection), IEC 60068-2 (environmental testing), IEC 60060-1 (high-voltage test techniques), IEC 60255-21 (vibration and shock) and IEC 61000-4-2, -3, -5, -6 and -8 (electromagnetic compatibility). Applications: phase and ground overcurrent protection (ANSI 50/51 and 50N/51N) and differential protection (ANSI 87) with relays that accept mV inputs, energy metering and distribution automation. Made in Brazil with HVEX technical support.