HVEX | Rapid Test Laboratory for Transformers

TEST LABS

Rapid Test Laboratory for Transformers

The HVEX Rapid Test Laboratory is an automated, container-based test line for routine tests on distribution transformers rated up to 36 kV and 5 to 300 kVA. After oil filling and thermal stabilization, the transformer enters the test module. The operator connects 8 cables (three-phase) or 5 cables (single-phase), closes the module and loads the unit record in the software, which fills in the test variables. The automated central bench connects and disconnects the instruments through a pneumatic circuit and runs the applied voltage, induced voltage, no-load loss and load loss tests with no operator intervention. Each unit is tested in 4 to 12 minutes, about 8 minutes on average. At the end, the HVEX Container Lab Acquisition software shows pass or fail and issues the test report.

Technical Information

Power supply
380 V three-phase, 200 kVA
Compressed air
3 to 6 bar, 0.5 m³/h flow
Area
Space for the 6.1 × 2.4 m container next to the production line
Transformers
Oil-filled and thermally stabilized before testing
Foundation
Level floor for 5,000 kg

A complete sequence with no manual cable changes

The transformer is connected only once. The automated bench switches the connections between the applied voltage (up to 70 kV), induced voltage (50 to 240 Hz source), no-load loss (up to 3400 V) and load loss tests, with 0.6 % voltage and current accuracy. The software compares the results with the record limits and releases the report.

HVEX | A complete sequence with no manual cable changes
HVEX | Benefits and Usability

Benefits and Usability

  • HVEX | ≈ 8 minutes per transformer
    ≈ 8 minutes per transformer

    Each unit is tested in 4 to 12 minutes, depending on power and voltage, keeping pace with the production line.

  • HVEX | Operator out of the circuit
    Operator out of the circuit

    Tests run with the module closed and no operator interaction while voltage is applied.

  • HVEX | Fewer wiring errors
    Fewer wiring errors

    Only 8 or 5 cables and pneumatic switching between tests: no manual connection changes.

  • HVEX | Ready to install
    Ready to install

    6.1 × 2.4 × 2.6 m container supplied at 380 V three-phase, installed next to the production line.

Rapid Test Laboratory highlights

Routine tests per ABNT NBR 5356 (IEC 60076) in an automatic sequence, with a report for every unit, for series production of distribution transformers.

  • HVEX | ImageAutomatic routine test sequence
  • HVEX | Image≈ 8 min per transformer
  • HVEX | ImageUp to 36 kV and 5 to 300 kVA
  • HVEX | ImageComplete laboratory in a container