TEST LABS
High-Frequency Current Transformer — HFCT
The HVEX HFCT is a high-frequency inductive sensor that detects the current pulses generated by partial discharges in transformers, cables, rotating machines, switchgear and other high-voltage equipment. Clamp-on, it opens and closes with one hand and is installed without electrical contact on the grounding lead or return path of the equipment — with no outage or change to the installation. With 1.0 V/A sensitivity into 50 Ω and a 1 kHz to 150 MHz band, it follows fast, low-amplitude pulses and strongly attenuates power-frequency current. The signal travels by coaxial cable to the acquisition system, which analyzes discharge amplitude, phase, repetition and patterns. It is the current sensor of HVEX partial discharge measurement and monitoring solutions, for spot tests or continuous monitoring.