High-Frequency Current Transformer — HFCT

The HVEX HFCT is a high-frequency inductive sensor that detects the current pulses generated by partial discharges in transformers, cables, rotating machines, switchgear and other high-voltage equipment. Clamp-on, it opens and closes with one hand and is installed without electrical contact on the grounding lead or return path of the equipment — with no outage or change to the installation. With 1.0 V/A sensitivity into 50 Ω and a 1 kHz to 150 MHz band, it follows fast, low-amplitude pulses and strongly attenuates power-frequency current. The signal travels by coaxial cable to the acquisition system, which analyzes discharge amplitude, phase, repetition and patterns. It is the current sensor of HVEX partial discharge measurement and monitoring solutions, for spot tests or continuous monitoring.

Technical Information

Installation point
Accessible grounding lead or return path, up to 26.9 mm
Cable
50 Ω coaxial to the acquisition system
Acquisition system
Input compatible with a band up to 150 MHz
Environment
0 to 65 °C
Safety
Safety clearances from energized parts during installation

Wide band for fast pulses

Between 1 kHz and 150 MHz the sensitivity is flat at 1.0 V/A. Nanosecond partial discharge pulses are recorded faithfully, while power-frequency current on the grounding is strongly attenuated.

HVEX | Wide band for fast pulses
HVEX | Benefits and Usability

Benefits and Usability

  • HVEX | Non-invasive installation
    Non-invasive installation

    Clamp-on, installed on the grounding with the equipment in service.

  • HVEX | High sensitivity
    High sensitivity

    1.0 V/A into 50 Ω, with 2.5 ns usable rise time.

  • HVEX | 1 kHz to 150 MHz band
    1 kHz to 150 MHz band

    Flat response for PD pulses and rejection of power frequency.

  • HVEX | Integrated with HVEX solutions
    Integrated with HVEX solutions

    Current sensor of HVEX PD measurement and monitoring systems.

HFCT highlights

The current sensor for insulation diagnostics in the field.

  • HVEX | Image1.0 V/A sensitivity
  • HVEX | Image1 kHz to 150 MHz band
  • HVEX | ImageClamp-on, no outage
  • HVEX | Image50 Ω BNC output

People who visited also viewed

Discover the future of energy with Hvex!

Subscribe to our newsletter to stay updated on the latest news!