HVEX | Fixed Partial Discharge Monitoring Panel

TEST LABS

Fixed Partial Discharge Monitoring Panel

The HVEX PD Panel is a fixed system for continuous partial discharge measurement and monitoring, permanently installed next to the asset. It combines an industrial computer, a high-speed digitizer and the HVEX PDMS software to acquire and analyze PD pulses from transformers, bushings, cables, generators and other equipment rated 13.8 to 500 kV. The sensors pick up the high-frequency pulses: couplers on the capacitive tap of condenser bushings and coupling capacitors act as capacitive dividers and high-pass filters (IEEE C57.113); where no tap is accessible, an HFCT on the grounding cable takes the reading. The panel digitizes the signals at 500 MSa/s and 12 bits, rejects noise with digital filters and computes the apparent charge per phase, in pC, per IEC 60270, every 5 minutes. It also records voltage, leakage current and the change in bushing tan δ and capacitance. Results are sent to the control center over Ethernet, optical fiber or GSM using Modbus TCP/IP and DNP 3.0, and the HVEX PD calibrator keeps the measurement traceable from commissioning.

Technical Information

Installation site
Next to the monitored asset, in an indoor or outdoor substation (IP54 panel)
Sensor access
Bushing capacitive tap, grounding cable or HV terminal, depending on the sensor
Cabling
Coaxial cables between the sensors and the panel
Communication
Ethernet, optical fiber or GSM coverage to the control center
Environment
−25 to +85 °C; humidity 5 to 95 % non-condensing

From PD pulse to asset diagnosis

In the HVEX PDMS software, every acquisition shows the pulses over the sine wave, the Lissajous figure and the FFT spectrum, already filtered. The history per asset and per phase reveals the trend in discharges and leakage current, so maintenance can be scheduled before a failure. Reports are generated in .pdf and .docx.

HVEX | From PD pulse to asset diagnosis
HVEX | Benefits and Usability

Benefits and Usability

  • HVEX | Continuous monitoring without an outage
    Continuous monitoring without an outage

    The installation is permanent: partial discharges are tracked in service, with no need to take the equipment offline to measure.

  • HVEX | Condition-based maintenance
    Condition-based maintenance

    The trend in apparent charge per phase shows how the insulation is evolving and helps schedule work before a failure.

  • HVEX | Three sensors for every type of asset
    Three sensors for every type of asset

    Capacitive tap coupler, HFCT on the ground lead or coupling capacitor, depending on the equipment and the access point.

  • HVEX | Traceable measurement from commissioning
    Traceable measurement from commissioning

    The HVEX PD calibrator injects known pulses from 5 to 1000 pC to adjust the measurement per IEC 60270.

PD Panel highlights

Three-phase partial discharge monitoring in pC, with tracking of bushing leakage current, tan δ and capacitance, in an IP54 stainless steel panel that reports to the control center.

  • HVEX | ImageApparent charge in pC per phase (IEC 60270)
  • HVEX | Image500 MSa/s, 12-bit digitization
  • HVEX | ImageModbus TCP/IP and DNP 3.0 over Ethernet, fiber or GSM
  • HVEX | ImageIP54 stainless steel panel with surge protection