HVEX

Command Palette

Search for a command to run...

HVEX | Medium-Voltage Vacuum Circuit Breaker 17.5 kV and 36 kV — Fixed or Withdrawable

PROTECTION

Medium-Voltage Vacuum Circuit Breaker 17.5 kV and 36 kV — Fixed or Withdrawable

The HVEX medium-voltage vacuum circuit breaker protects, controls and switches 17.5 kV and 36 kV circuits in metal-clad switchgear, MV panels, compact substations and industrial and utility substations. Vacuum interrupters quench the arc quickly and safely without SF6 gas and provide long service life even under frequent switching duty. The spring-operated mechanism, charged by motor or manually with a crank, allows local or remote closing and opening. Auxiliary contacts and position indicators integrate the breaker with protection relays, such as HVEX relays, and with SCADA systems. Supplied in fixed or withdrawable versions, defined at quotation. In the 17.5 kV version, rated currents range from 630 A to 1600 A, with short-time withstand current up to 31.5 kA for 4 s, 95 kV BIL and operating sequence O-0.3s-CO-180s-CO (full data in the table). The 36 kV version has 185 kV BIL and 31.5 kA for 4 s. Reference standard: IEC 62271-100 (high-voltage alternating-current circuit breakers). Typical applications: MV switchgear and compact substations, industrial and utility substations, protection of transformers, generators and motors, and power distribution centers.

Technical Information

Rated voltage
17.5 kV
Voltage withstand for 1 minute at industrial frequency (Open contacts)
50 kV
Impulse voltage withstand (Open contacts)
95 kV
Rated current
630, 1250, 1600 A
Short-time withstand current
20, 25, and 31.5 kA
HVEX | Benefits and Usability

Benefits and Usability

  • HVEX | Status Indicators
    Status Indicators

    Various status indicators such as energization, general operation and spring load.

  • HVEX | High Insulation
    High Insulation

    High insulation and arc extinguishing capacity during switching.

  • HVEX | Manual Operation
    Manual Operation

    Using a crank, it is possible to load the springs in order to operate the circuit breaker manually, whether when empty or in an emergency.

  • HVEX | Transport and Lifting
    Transport and Lifting

    It has its own eyelets for correct weight distribution when lifting and transporting the equipment.

Exclusive Features

Two-year warranty against manufacturing defects. Can be combined with HVEX protection relays and the Shield-X platform for a fully compatible protection solution.

  • HVEX | ImageGreater reliability
  • HVEX | ImageFast operation
  • HVEX | ImageSafety and precision

Related Articles