HVEX | Insulating Oil Breakdown Voltage Tester

TEST LABS

Insulating Oil Breakdown Voltage Tester

The HVEX Insulating Oil Breakdown Voltage Tester measures the dielectric strength of mineral oils and other transformer insulating liquids — one of the most widely used tests to assess oil on receipt, after treatment and during maintenance. The sample is placed in the test cell, between two electrodes with an adjusted gap. After the standing time, the AC voltage is raised at the programmed rate until breakdown; the instrument cuts the voltage, records the value and repeats the cycle for the programmed number of times (1 to 9). The individual values and the mean are shown on the LCD, saved in memory and printed on the built-in printer. The RS232 interface sends results to a computer, and the instrument displays the ambient temperature and humidity of the test. Compact and portable, with overvoltage and overcurrent protection, it serves laboratories and field tests, with programmable parameters for methods such as IEC 60156.

Technical Information

Power supply
220 VAC ± 10%, 50/60 Hz, with 200 W available
Grounding
Grounding terminal connected before energizing the instrument
Sample
Collected in a clean, dry container; cell rinsed with the sample oil
Environment
0 to 40 °C and relative humidity below 85%
Method
Test cell and electrodes per the adopted method (e.g., IEC 60156)

Automatic test, from standing time to result

Rise rate, standing time, interval and number of breakdowns are programmed once. The instrument then runs the whole cycle, cuts the voltage at each breakdown and delivers the calculated, printed mean, with less operator influence.

HVEX | Automatic test, from standing time to result
HVEX | Benefits and Usability

Benefits and Usability

  • HVEX | Up to 100 kV
    Up to 100 kV

    Output voltage from 0 to 100 kV, with waveform distortion below 3%.

  • HVEX | Programmable parameters
    Programmable parameters

    0.5 to 5 kV/s rise, standing time, interval and 1 to 9 breakdowns per test.

  • HVEX | Results printed on site
    Results printed on site

    Values and mean on the LCD, in memory, on the built-in printer and over RS232.

  • HVEX | ± 3% accuracy
    ± 3% accuracy

    Accurate breakdown voltage measurement, with automatic voltage cut-off.

Tester highlights

Insulating oil dielectric strength with an automatic, repeatable test.

  • HVEX | ImageOutput voltage up to 100 kV
  • HVEX | ImageAutomatic test cycle
  • HVEX | ImageBuilt-in printer and RS232
  • HVEX | ImageFor transformer oil